Skip to main content

Veikong Electric

Author: Veikong Electric

Over-Excitation

Over-Excitation Braking or Braking Resistor: Which One Should a VFD Use? 

Introduction  When a motor-driven machine slows down, its stored mechanical energy does not disappear immediately. The rotating load can drive the motor like a generator and return energy to the VFD DC bus. If that energy accumulates faster than the drive can handle it, the DC-bus voltage rises and the VFD may trip on overvoltage.  Over-excitation braking and a braking resistor are two common ways to improve deceleration. They are not equivalent solutions. The correct choice depends on the amount of regenerative energy, stopping time, braking frequency, load direction, and thermal limits of the motor and braking components.  Why Does DC-Bus Overvoltage Occur During Deceleration?  During normal motoring, electrical energy flows from the supply through the VFD to the motor. During rapid deceleration, a high-inertia load continues rotating and drives the motor. The energy then flows back toward the DC bus. A standard diode-front-end VFD cannot normally return this energy to the power grid, so the DC voltage increases.  Extending the deceleration time reduces the rate of regenerated energy and is often the first adjustment to consider. However, some processes require a short stopping time, and some loads regenerate continuously or repeatedly. In those cases, an additional braking method is needed.  What Is Over-Excitation Braking?  Over-excitation braking increases motor excitation during deceleration so that part of the mechanical energy is converted into heat inside the motor. It can strengthen the braking effect without an external resistor and can be useful for occasional stops or moderate regenerative energy.  Its capacity is limited by the motor’s thermal condition and by the control strategy of the drive. Repeated or prolonged use can increase motor temperature, and the available braking torque may not be sufficient for a high-inertia machine or a very short deceleration time. Over-excitation braking should therefore not be presented as a universal replacement for a braking resistor.  How Does a Braking Resistor Work?  A braking transistor or external braking unit monitors the DC-bus voltage and switches regenerated energy into a braking resistor. The resistor converts the electrical energy into heat outside the motor. This provides a defined path for larger or more frequent braking energy and helps prevent DC-bus overvoltage.  The resistor must be selected according to the drive specification, minimum permitted resistance, peak braking power, average power, and duty cycle. Some VFD ratings include a braking transistor, while others require an external braking unit. The resistor also needs adequate ventilation and safe clearance because its surface temperature can become very high.  When Is Over-Excitation Braking Suitable?  Over-excitation braking can be considered when stops are occasional, load inertia is moderate, the deceleration time is not extremely short, and the motor has sufficient thermal margin. Typical examples may include machines that need a firmer stop than a natural coast-down but do not generate large amounts of energy in every cycle.  It can also be useful when installation space is limited or an external resistor is undesirable. Even so, the motor temperature and actual stopping performance should be verified during commissioning. If overvoltage trips continue, simply increasing excitation is not a safe substitute for analyzing the braking energy.  When Should a Braking Resistor Be Used?  A braking resistor is usually the more appropriate choice for repeated rapid stops, large-inertia loads, short cycle times, or overhauling loads that can drive the motor. Examples include centrifuges, high-speed spindles, unwinders, reciprocating machines, and some crane or hoist movements.  For lifting applications, the resistor only manages electrical braking energy. It does not hold a suspended load and cannot replace a properly designed mechanical brake or safety system. If the load regenerates continuously or the braking energy is very large, a regenerative drive or active front end may be more suitable than a conventional resistor system.  Can Both Methods Be Used Together?  Depending on the VFD model and control strategy, over-excitation braking may be used together with a braking resistor. Motor loss can absorb part of the energy, while the resistor handles the energy that raises the DC bus above the braking threshold. This can improve deceleration performance in some applications.  However, combined operation does not remove the need to calculate resistor resistance, power, and duty cycle. The final selection should be based on the machine’s maximum speed, total inertia, required stopping time, cycle frequency, and potential energy from vertical movement.  Common Selection and Installation Mistakes  Common mistakes include setting an unrealistically short deceleration time, choosing a resistor only by motor power, using resistance below the drive’s permitted minimum, ignoring braking duty, or installing the resistor inside a poorly ventilated control cabinet. Connecting a resistor to a drive that requires an external braking unit is another serious error.  Commissioning should include repeated-stop testing under the heaviest expected load. Engineers should monitor DC-bus voltage, motor temperature, resistor temperature, stopping time, and fault history. Protective devices and wiring must follow the VFD and braking component manuals.  Choosing a Braking Method for VEIKONG Drives  VEIKONG drives provide braking functions according to the selected series and rating. When planning a system, users should confirm whether the drive has an internal braking transistor, requires an external braking unit, and supports the intended control function. The motor, VFD, resistor, and machine duty must be considered as one system.  Over-excitation braking is a practical option for moderate and intermittent deceleration, while a correctly sized braking resistor offers greater energy-handling capability for frequent or demanding stops. A clear calculation and real-load test will produce a safer and more reliable result than selecting either method by habit. 

Read More »
Motor Auto-Tuning

Why Is Motor Auto-Tuning Important Before Running a VFD?

Introduction  A variable frequency drive can often start a motor after only the basic nameplate data have been entered. However, successful rotation does not necessarily mean that the drive has an accurate model of the motor. For applications that require strong low-speed torque, stable current control, fast response, or precise speed regulation, motor auto-tuning is an important part of commissioning.  Auto-tuning allows the VFD to identify electrical characteristics that cannot be fully described by rated voltage, current, frequency, speed, and power alone. With more accurate motor parameters, the drive can calculate the appropriate voltage and current commands more effectively and make vector control perform as intended.  What Is Motor Auto-Tuning?  Motor auto-tuning, also called motor identification or parameter identification, is a procedure in which the VFD tests the connected motor and calculates parameters for its internal motor model. Depending on the drive, motor type, and selected control mode, these may include stator resistance, leakage inductance, magnetizing characteristics, no-load current, or rotor-related parameters.  The exact parameters identified are not identical on every VFD. The important point is that the drive is learning the actual electrical behavior of the connected motor instead of relying only on default values. This is especially relevant in sensorless vector control and closed-loop vector control, where torque-producing current and magnetizing current must be separated and regulated accurately.  Why Are Nameplate Parameters Not Always Enough?  Two motors with the same rated power can have different winding designs, efficiencies, power factors, current characteristics, and magnetic behavior. Cable length, motor temperature, rewinding history, and the way the motor is connected can also affect the values seen by the drive.  Nameplate data provide the essential starting point, but they do not describe every parameter required by a high-performance control algorithm. If the VFD uses an inaccurate motor model, the motor may still run, but its low-speed torque, current stability, speed estimation, and dynamic response may be weaker than expected.  Static Auto-Tuning and Rotating Auto-Tuning  Static auto-tuning is performed without intentionally rotating the motor shaft. It is useful when the motor cannot be disconnected from the machine or when rotation during commissioning would be unsafe. The VFD applies test signals and identifies the parameters that can be measured while the rotor remains stationary. It is convenient, but the completeness and accuracy of the result depend on the motor and drive design.  Rotating auto-tuning allows the motor to turn during identification. It can normally obtain a more complete motor model because the drive can observe the motor under rotation. Before this procedure, the motor should be uncoupled from the load or confirmed to be safely unloaded, and the area must be cleared. Rotating tuning should not be performed casually on hoists, loaded conveyors, pumps with process constraints, or machines whose direction of rotation has not been verified.  What Problems Can Incorrect Tuning Cause?  Incorrect or missing motor parameters may lead to weak torque at low speed, unstable current, inaccurate speed estimation, slow torque response, increased heating, or unexpected overcurrent trips during acceleration. These symptoms do not always prove that auto-tuning is the only issue, but motor data should be checked early during troubleshooting.  A tuning result can also be wrong if the nameplate data were entered incorrectly, the motor was wired in a different star or delta connection from the setting, an output contactor opened during the test, or the motor was already turning. For this reason, preparation is as important as the tuning command itself.  A Practical Auto-Tuning Procedure  First, confirm the motor type and enter the nameplate voltage, current, frequency, speed, and power accurately. Check the motor wiring and make sure the VFD output is connected directly to the intended motor during identification. Select the correct control mode and the tuning method permitted by the machine.  Next, secure the equipment. If rotating tuning is selected, disconnect or safely unload the driven machine, confirm the rotation direction, and keep personnel away. After tuning is completed, save the parameters and test the motor at low speed before increasing the command. Observe current, direction, vibration, noise, and load response. The final test should be performed under real operating conditions.  Does Every VFD Application Require Auto-Tuning?  Simple fan or pump applications using basic V/F control may operate adequately with correct nameplate data and default motor parameters. In contrast, sensorless vector control, closed-loop vector control, permanent-magnet motor control, high starting torque, and demanding speed-response applications benefit much more from accurate identification.  Auto-tuning should therefore be selected according to the control objective rather than treated as an automatic ritual. The commissioning engineer should also follow the drive manual because the permitted tuning method, motor conditions, and safety requirements vary by model.  Applying Motor Identification with VEIKONG Drives  VEIKONG variable frequency drives provide motor parameter identification functions according to the selected model, motor type, and control mode. Correct nameplate entry, appropriate tuning selection, and a controlled test run help the drive establish a more accurate motor model and deliver the intended control performance.  For applications that require strong low-speed torque or faster dynamic response, auto-tuning should be considered part of a complete commissioning process. It does not replace correct sizing, wiring, mechanical inspection, or protection settings, but it gives the VFD a more reliable foundation for controlling the motor. 

Read More »
Injection Molding Machines

VFD for Injection Molding Machines: How Variable Speed Control Improves Production Efficiency 

Plastic parts come off injection molding machines by the thousands, and every one of them starts with a motor turning an oil pump. Most injection molding machines on the market are hydraulically driven. The oil pump supplies the power, and the motor behind it decides how much that power costs to produce.  The problem is that the machine never needs the same amount twice in a row. A single cycle moves through several steps, and each step wants a different flow and pressure. A motor running at one fixed speed cannot follow those changes. A variable frequency drive (VFD) can.  This post explains where energy is lost in a hydraulic injection molding machine and how variable speed control addresses it.  How a Hydraulic Injection Molding Machine Works  The machine follows a set order of steps in every cycle:  Each step depends on careful coordination of time, pressure, speed, and position. Every movement has its own matching pressure and speed, and those values change with position and time. When one step finishes, a signal goes to the program controller. The controller then sends the order for the next step.  The load swings a lot from one stage to the next. That is the starting point for the energy problem.  Where a Traditional Machine Wastes Energy  A traditional machine uses a constant pump to supply oil. The motor holds one speed for the whole cycle, so the oil supply stays fixed. Yet the work is intermittent, so the machine is rarely fully loaded.  The extra energy has to go somewhere. It ends up in the damper, in leakage from the oil circuit, and in heating the oil. That creates further problems:  Measurements show that at least 50% of the energy is wasted in a fixed oil-supply system.  What Does a VFD Do on an Injection Molding Machine?  A VFD is an electronic system that controls an AC induction motor. It can control torque, speed, and motor direction, and it starts the motor smoothly at a controlled acceleration rate.  On an injection molding machine, the drive does three main things:  The result is that pump flow and pressure match what the system needs at that moment, and nothing more.  How Variable Speed Control Improves Production Efficiency  Efficiency in molding is about more than the power bill. A VFD brings several benefits to injection machine applications:  Less wasted oil heat also means less strain on the valves and the oil circuit, which are the parts that suffer when energy is wasted.  How Much Energy Can a VFD Save?  On injection machines, power savings can reach 30% to 70%. For the VFD550I drive described below, the comprehensive power saving rate is 20% to 60%. Actual results depend on the machine and how it is used.  Veikong’s VFD550I for Hydraulic Applications  Shenzhen Veikong Electric Co. Ltd. is an AC drive company that researches, manufactures, and trades high-, medium-, and low-voltage frequency inverters. It has operated since 2004. For injection molding, Veikong offers the VFD550I Electro-Hydraulic Servo Inverter.  The VFD550I is designed for hydraulic control. It has a built-in pressure control algorithm that is fast, accurate, and stable. It can be used for energy-saving transformation of injection molding machines, die-casting machines, hydraulic stations, and electric melt adhesives.  Key specifications:  The drive also includes AI zero-drift automatic correction and supports common incremental encoders and rotary transformers. It handles both closed-loop and open-loop vector control.  How Precise Is the Pressure Control?  The closed-loop pressure algorithm lets the speed and pressure of the injection molding system follow commands quickly and steadily. The figures are:  Steady pressure matters because every step in the cycle depends on it.  FAQs (Frequently Asked Questions)  1. Which Veikong drive is made for injection molding machines?  The VFD550I Electro-Hydraulic Servo Inverter is made for injection molding machines.  2. Can it run on different motor types?  Yes, it supports asynchronous motors and permanent magnet synchronous motors.  3. What voltage does it use?  It uses a voltage of 380 V to 480V.  4. Does it help when the machine is idle?  Yes, stopping the motor while the machine is off-duty, mainly during cooling, saves more energy.  5. Are manuals available?  Yes, a catalogue and a user manual are available for the VFD550I.  Summary  Hydraulic injection molding machines need different flow and pressure at each step, but a fixed-speed motor cannot follow. In a traditional system, at least 50% of the energy is wasted, and the waste shows up as oil heat, valve wear, and noise.  A VFD changes the picture by adjusting motor speed at each step and stopping the motor when it is idle. Power savings of 30% to 70% are possible on injection machines, along with soft starts, lower noise, and easier operation. The VFD550I adds a dedicated pressure control algorithm, support for two motor types, and a range from 0.7kW to 710kW.  If you are planning an energy-saving upgrade for an injection molding machine, the Veikong team can help you choose the right drive. Reach out to them to talk through your application.

Read More »
IP55 VFD

IP55 VFD for Harsh Industrial Environments: Benefits, Applications, and Selection Guide 

A variable frequency drive, or VFD, controls the speed and torque of an AC motor. In many plants, it is installed close to the motor, and that location is often demanding. Dust, moisture, and temperature swings all put steady pressure on the electronics inside.  Drive manufacturers recognize these risks. Troubleshooting guidance for VFDs notes that conductive contaminants such as dust and moisture can cause failures. Over-temperature can lead to early failure, while low temperature can cause condensation that damages components. Blocked cooling is another concern, which is why fans and heatsinks should be cleaned monthly.  For this reason, the protection level of a drive deserves as much attention as its power rating. This guide explains what an IP55 VFD is, what benefits it offers, where it fits, and how to select one for a demanding site.  What Is an IP55 VFD?  A VFD is an electronic system that controls an AC induction motor. It manages speed, torque, and direction, and it brings the motor up to speed at a controlled rate.  An IP55 VFD does the same job with a high protection level. Veikong presents its VFD510 IP55 as a high-protection AC drive for harsh environments.  Why Harsh Sites Are Hard on Drives  Several common causes of drive trouble are worth knowing about:  Benefits of the VFD510 IP55 VFD  The VFD510 IP55 is a 380V drive covering 2.2 kW to 45 kW, and the page also mentions higher power. Its feature list is short and practical:  Two other design points are worth knowing. The heat dissipation design allows continuous stable operation in high-temperature environments. The circuit boards also get at least three layers of automatic three-proof paint coating for harsh environment adaptability.  The VFD510-PV IP55 for Solar Pumping  Veikong also offers an IP55 drive made for solar pump systems. Its high protection level suits harsh environments. Key points:  Where an IP55 Drive Fits  For harsh environments, Veikong offers IP55 high-protection frequency converters. The VFD510-PV IP55 carries that protection into solar pumping.  Across its whole range, Veikong products are widely used in petroleum, chemical, melting, hoisting, electric power, building materials, water supply, plastics, textiles, printing and packing. They also serve manufacturing, water treatment, HVAC, agriculture, and automation. Application solutions cover pumps, air compressors, hoists and cranes, injection machines and washing machines.  Those lists describe the full Veikong range, not only the IP55 model. So check your own site conditions before you pick a drive.  How to Select an IP55 VFD  Veikong provides free professional product selection based on the application scenario, as part of its pre-sales service for premium distributors. Whether you plan to ask for that help or choose on your own, work through these points first.  Start with the Site  Look at dust, damp, and heat. Then compare your ambient temperature with the 50℃ standard design. Veikong also suggests asking operators about machine status, grid fluctuations, nearby construction, and power-factor capacitor switching, since outside causes are often mistaken for drive faults.  Match Voltage and Power   Match the Load  Decide whether your load is heavy or light. The G/P combination covers both.  Count the Motors and Check the Connections   The drive supports multiple motors and multiple communication interfaces. List what your control system needs before you order.  Plan Safety and Options  The STO interface is standard. For solar pumping, decide whether you want the optional LCD keypad or GPRS monitoring.  Look at Nearby Options   Veikong also offers a VFD510 IP54 drive in its Special VFD range. It can design an IP54 soft starter control cabinet on request.  Built and Tested Before Delivery  Every Veikong product passes these checks before delivery:  The delivery failure rate stays at 0.5%. Quality is managed under the ISO9001 standard, and the products have passed CE certification. They also meet international standards including ISO, CE, and IEC. Veikong’s R&D team has 20 years of industry experience and holds 52 technical patents.  FAQs (Frequently Asked Questions)  1. What power range does the VFD510 IP55 cover?  380V, 2.2 kW to 45 kW, with higher power also available.  2. Can it run more than one motor?  Yes, the drive supports multiple motors.  3. What is the delivery time?  Orders under 10 units are in stock or delivered within 3 days. Orders within 100 units take 7 to 14 working days.   4. What warranty comes with it?  There is a 24-month after-sales warranty with free spare parts for component quality issues. Support also includes lifelong online technical support, a 24-hour fast response, and software update solutions within 2 hours.  5. Can Veikong customize a drive?  Yes, it offers logo customization, plus software and parameter optimization.  Summary  Dust, moisture, and temperature swings are what wear drives down on rough sites. A high protection level is one way to deal with that. The Veikong VFD510 IP55 offers IP55 protection, a 50℃ ambient temperature standard design, a standard STO interface, heavy and light load G/P duty, multiple motor support, and several communication interfaces.  For solar pumping, the VFD10-PV IP55 adds MPPT tracking of 99.5% or higher and hybrid AC and DC switching.  If you are choosing a drive for a demanding site, visit veikong-electric.com to download the VFD510 IP55 catalogue and user manual, then reach out to the Veikong team for selection help. 

Read More »
VFD500Plus

From Proven Performance to Greater Possibilities: VEIKONG Launches VFD500Plus

A Proven Platform Continues to Evolve  VEIKONG is pleased to introduce VFD500Plus, the next evolution of the proven VFD500 high-performance vector drive platform. For many years, VFD500 has served customers across a wide range of industrial applications and has built a strong reputation for stable operation, practical functions and reliable motor control. It has been one of VEIKONG’s important general-purpose drive products and a dependable choice for machine builders, system integrators and end users.  VFD500Plus builds on that established foundation. The “Plus” designation represents continuity as well as progress: the new series retains the practical general-purpose positioning of VFD500 while expanding motor compatibility, control performance, functional safety, communication options and system scalability. It is designed for customers who value the proven strengths of VFD500 but need additional capabilities for newer machines and more connected industrial systems.For users and service teams already familiar with VFD500, this development path also creates a clear product logic. Existing VFD500 experience remains valuable, while VFD500Plus provides a higher-specification option when new projects introduce more demanding motion control, safety integration or network requirements. Customers can therefore select the appropriate platform according to actual application needs rather than treating every project as requiring the same drive configuration.  Broader Motor Compatibility  VFD500 has provided mature control for asynchronous motor applications in many industries. VFD500Plus extends this capability to a wider range of motor technologies. In addition to asynchronous motors, it supports surface-mounted permanent magnet synchronous motors, interior permanent magnet synchronous motors and synchronous reluctance motors.  This broader compatibility allows equipment manufacturers to use one drive platform across more machine designs. Whether a project focuses on traditional induction motors, higher-efficiency permanent magnet motors or newer synchronous reluctance solutions, VFD500Plus provides greater flexibility for product development, upgrading and standardization.  Enhanced Vector Control and Low Speed Performance  Building on the V/F and sensorless vector control experience of VFD500, VFD500Plus provides V/F control, sensorless vector control and closed-loop vector control with a speed sensor. Its speed regulation range reaches 1:100 under V/F control, 1:200 under sensorless vector control and 1:1000 under closed-loop vector control.  The drive also delivers strong low-speed load capability: 150% at 0.5 Hz in V/F mode, 180% at 0.25 Hz in sensorless vector mode and 180% at zero speed in closed-loop vector mode. These improvements give users more control headroom in applications requiring stable starting, accurate speed regulation, rapid load response or dependable torque at very low speed.  A Wider Power Range and Stronger System Scalability  VFD500Plus covers power ratings from 0.4 kW to 1000 kW, allowing the same product family to support compact machinery as well as large industrial systems. The expanded range helps customers reduce the need to combine unrelated drive platforms when equipment portfolios include both low-power and high-power machines.  Two motor parameter groups, multiple acceleration and deceleration settings, process PID, simple PLC logic, multi-step speed operation, skip frequency and V/F separation further improve adaptability. These functions support different operating conditions without losing the straightforward commissioning approach expected from a general-purpose drive.  Functional Safety and Reliability Upgrades  Dual Safe Torque Off inputs are standard on VFD500Plus. In an appropriately designed safety system, STO can prevent the drive from producing motor torque and gives machine designers a more convenient basis for integrating functional safety. The final safety architecture should always be evaluated according to the machine, risk assessment and applicable standards.  Reliability has also been further strengthened through thermal simulation, optimized heat dissipation and an independent air duct that helps reduce dust entry into the drive. A large-air-volume, long-life cooling fan and enlarged aluminum heat-sink fins support temperature control. Comprehensive protection functions cover conditions including phase loss, overcurrent, motor overload, drive overload, overtemperature, ground short circuit, motor overspeed, speed deviation and PID feedback loss.  More Communication and Expansion Choices  VFD500Plus retains standard Modbus communication and adds a broader range of optional network solutions, including CANopen, EtherCAT, PROFINET, Modbus TCP, Ethernet and BACnet. This makes the drive easier to integrate into PLC systems, industrial Ethernet networks, building automation and more advanced machine architectures.  Encoder expansion options include incremental encoders, resolvers and Tamagawa-protocol absolute encoders. Users can also select a standard digital keypad, an optional dual-display keypad or an optional LCD keypad. Together with expandable I/O and communication options, these choices make configuration more flexible while keeping the standard product practical.  Smooth Operation for Modern Industrial Applications  Speed tracking start allows VFD500Plus to identify and smoothly restart a motor that is still rotating, helping reduce current and mechanical shock on fans, pumps and other inertia loads. Over-excitation can assist deceleration in suitable applications, while under-voltage stall prevention helps the motor decelerate in a controlled manner during a momentary power interruption and supports recovery after power returns.  VFD500 remains a proven high-performance platform whose reliability has been demonstrated through years of industrial use. VFD500Plus carries that experience forward and adds more capability for projects that require multiple motor types, higher control accuracy, functional safety, broader connectivity or a larger power range. With this launch, VEIKONG offers customers a stronger and more future-ready general-purpose drive platform without losing the practical engineering foundation that made VFD500 successful. 

Read More »
How Much Energy Can a VFD Save on Pumps and Fans

How Much Energy Can a VFD Save on Pumps and Fans? Affinity Laws and a Worked Savings Calculation 

Most pumps and fans are sized for the hardest day of the year. The motor is chosen for peak demand, then it spends years on easier days. One boiler plant, for example, ran at about 66% load most of the time. The fan motor still ran at full speed while a damper choked the airflow down to what the boiler needed.  The gap between what the machine can deliver and what the process needs is where the electricity goes. A variable frequency drive (VFD) closes it by changing motor speed instead of fighting the flow.  This post covers the affinity laws, two worked calculations, and a measured fan retrofit.  The Short Answer  How much energy can a VFD save on a pump or fan? It depends on how the machine is loaded, but the numbers can be large.  What the Affinity Laws Say  The affinity laws describe how a pump or fan responds when its speed changes. They apply to pumps just as they do to fans. Three links matter:  The third link drives the savings. Slow a pump a little and power drops a lot, which is why a VFD can cut energy use by more than the speed change alone would suggest.  Why Valves and Dampers Waste Energy  Throttling changes flow but leaves motor speed alone. Here is how common setups behave:  A VFD slows the pump instead. The same reduced flow is reached at lower pressure. Lower pressure can mean longer pump seal life, less impeller wear, and less vibration and noise.  Worked Example One: A Pump Slowed from 1200 to 700 GPM  Take a hydronic pump that must drop from 1200 GPM to 700 GPM. Those are the flow figures VEIKONG uses in its pump guidance. The steps look like this:  Treat 80% as the best case, because it assumes little or no static head. Static head is the height the pump must lift the water, regardless of the flow. When it is high, the system curve moves toward constant pressure and the savings shrink. The lower the static head, the greater the savings.  Worked Example Two: A Boiler Fan Retrofit with Measured Results  One VEIKONG oil industry application covers an energy-saving retrofit at a Chinese oil industry company. The plant had six boilers, each with ID, FD, and SA fans. The motors were sized for maximum load, yet the boilers mostly ran at 66% load, and dampers controlled the air. In May 2006, the three fans of the 4# boiler were converted to variable frequency control. Each drive ran one fan motor, and a bypass circuit let the motor run directly on line during drive downtime or maintenance.  The measured yearly results:  The arithmetic is short. Subtract the after figure from the before figure to get kWh saved. Divide that by the before figure for the saving rate. Multiply the kWh saved by the power price for the money saved.  Load changed the result. At 140 t/h of steam flow, the three fans drew about 1,273 kW less than before. At 200 t/h, the gap was about 905 kW. The boiler ran at 140 to 150 t/h for around eight months of the year and at 200 t/h for just two, so the bigger savings landed in the long months.  Other gains came with it:  What Decides Your Own Savings  Three things shape the result:  To judge a pump, you need its curves. Pump curves come from the manufacturer. System curves are harder to get, but a quick method gives a fair estimate:  VEIKONG Drives for Pump and Fan Control  Shenzhen VEIKONG Electric Co., Ltd has researched, manufactured, and traded high-, medium-, and low-voltage frequency inverters since 2004. Several products suit pump and fan work:  VEIKONG products follow ISO9001 quality management and meet ISO, CE, and IEC standards. Each unit passes a 12-hour power-on aging test in a high-temperature chamber and a final full-load test before delivery.  Summary and Next Steps with VEIKONG  Power follows the cube of speed, so a modest speed cut brings a large power cut. The pump example reaches a best case near 80%. The boiler fan retrofit measured 49.5% and paid for itself within the year.   Valves, dampers, and bypass lines throw that potential away. Your own number depends on part-load hours, static head, and how flow is controlled today.  Send VEIKONG your motor data, flow range, and current control method. The team offers free professional product selection based on your application. 

Read More »
VFD vs Frequency Inverter vs Frequency Converter vs Servo Drive

VFD vs Frequency Inverter vs Frequency Converter vs Servo Drive: What’s the Difference? 

Walk through a plant, and you will hear four names for what looks like the same box on the wall: VFD, frequency inverter, frequency converter, and servo drive. Buyers often ask if these are four different products. Some of the names describe one thing, and one of them describes a different job.  Utility power arrives at a fixed frequency. A drive lets a motor run at other speeds, so one motor can handle work that changes. Drives have also become compact and versatile, since microprocessors replaced older solid-state elements.  You can find them in petroleum, chemical, hoisting, water supply, plastics, textiles, printing, and packing. With that many uses, the naming gets messy.  The Short Answer  VFD, frequency inverter, and frequency converter point to the same family of devices. A servo drive is the one with a different focus: position control and precision.  What Is a VFD?  A VFD starts a motor smoothly and brings it up to the desired speed at a controlled acceleration rate. It also controls torque and direction. That means one motor can serve jobs that need different speeds.  A VFD system has three parts:  People usually pick a VFD for these reasons:  Frequency Inverter and Frequency Converter: Same Idea, Different Words  Veikong’s own pages show how loosely these terms get used. The pump page talks about frequency converters, while the product lines are called frequency inverters and VFDs. They describe the same drive doing the same work.  Pumps make a clear example. When a drive slows a pump, the pump curve shifts down. The system reaches the same reduced flow it would get from a valve, such as 700 GPM down from 1200 GPM, but at a lower pressure.  Lower pressure can mean longer pump seal life, less impeller wear, and less vibration and noise. Because of the affinity laws, power drops sharply at reduced flow. That drop is where the savings come from.  Typical pump uses include:  Where a Servo Drive Is Different  The S6 shows what sets a servo drive apart. It is a spindle-dedicated servo drive, built to run the spindle motors of CNC lathes, milling machines, machining centers, and grinders. It brings position control and encoder interfaces that a plain speed drive does not focus on.  Key details of the S6:  There is also a middle ground. The VFD550I electro-hydraulic servo inverter is made for hydraulic control.  It supports asynchronous and permanent magnet synchronous motors, and it handles pressure control under encoderless vector control with built-in pressure control algorithms. It suits injection molding machines, die-casting machines, and hydraulic stations.  Which One Fits Your Machine?  Match the drive to the job:  Veikong’s Drive Range at a Glance  The range also includes the VFD 500, VFD 530, and VFD 550 AC drives, plus bypass soft starters.  Why Buyers Look at Veikong Electric  Shenzhen VEIKONG Electric Co. Ltd. is an AC drive enterprise founded in 2004. It researches, manufactures, and trades high-, medium-, and low-voltage frequency inverters, with general purpose VFDs available up to 1000kW.  Its R&D and management team brings more than 20 years of experience in research, product development, and quality management.  Summary  VFD, frequency inverter, and frequency converter are three names for one kind of drive, which controls the speed, torque, and direction of an AC motor. Veikong’s general purpose VFDs cover power ratings up to 1000kW.  A servo drive such as the S6 goes further with position control, spindle orientation, and encoder interfaces. The VFD550I sits between the two for hydraulic pressure control.  Not sure which drive suits your machine? Send the Veikong team your motor and application details, and they will help you select the right one. 

Read More »
VEIKONG Concludes a Successful Showcase at CIIF 2026 in Shanghai

VEIKONG Concludes a Successful Showcase at CIIF 2026 in Shanghai

From October 12 to 16, VEIKONG participated in the 2026 China International Industry Fair in Shanghai, presenting a focused selection of variable frequency drives and motor control solutions to visitors from China and overseas markets. The five-day event provided an important opportunity to meet customers face to face, discuss real application requirements, and exchange ideas with professionals from across the industrial automation sector.  At Booth F128 in Hall 8.1, the VEIKONG team welcomed visitors from different industries and introduced solutions for general motor control, high-performance applications, solar pumping, machinery, fans, pumps, and other industrial systems. Rather than simply displaying individual products, the team focused on how drive technology can be matched to operating conditions, motor characteristics, control requirements, and long-term maintenance needs.  A Closer Look at VEIKONG Drive Solutions  The booth featured a range of VEIKONG products, from compact variable frequency drives to high-performance drive platforms. Visitors were able to see the equipment at close range, compare different product formats, and learn more about functions for speed regulation, torque control, energy-saving operation, communication, and system integration. The display also included control boards and product materials that helped explain the structure and capabilities behind the finished drives.  Particular attention was given to solutions for customers who need more than a standard start-and-stop function. Many discussions focused on stable control under changing loads, application-specific parameter settings, compatibility with different motors, and the importance of selecting the correct drive according to the real working environment. These conversations reflected a clear market demand for products that combine dependable hardware with practical technical support. Conversations Built Around Real Applications  One of the most valuable parts of CIIF was the opportunity to hear directly from users, distributors, engineers, and system integrators. Visitors shared questions about machine tools, pumping systems, ventilation, lifting equipment, production lines, and energy-efficiency upgrades. These discussions allowed the VEIKONG team to better understand the technical priorities and commercial expectations found in different markets.  For VEIKONG, this kind of communication is essential. A suitable drive solution depends not only on power and voltage, but also on load type, operating cycle, installation environment, braking requirements, communication method, and the customer’s service expectations. By discussing these details at the booth, the team was able to provide clearer product recommendations and identify areas for future product and service improvement.  Learning from a Wider Automation Ecosystem  CIIF also offered a valuable view of the broader direction of industrial automation. Across the exhibition halls, companies presented robotics, motion control, precision manufacturing, digital systems, and integrated automation solutions. The event showed that customers are increasingly looking beyond individual components. They expect equipment to work as part of a coordinated system that improves productivity, reliability, energy efficiency, and ease of maintenance.  This trend reinforces VEIKONG’s commitment to developing practical drive products while strengthening application support. Reliable performance remains the foundation, but the ability to respond to real operating challenges, support system integration, and communicate efficiently with customers is becoming equally important.  Thank You for Meeting VEIKONG in Shanghai  VEIKONG sincerely thanks everyone who visited the booth, shared project information, discussed technical questions, or simply stopped to learn more about the brand. Every conversation contributed to a better understanding of the market and opened new possibilities for cooperation.  The exhibition may have concluded, but the conversations will continue. VEIKONG will follow up with the customers and partners we met in Shanghai and continue providing variable frequency drives, solar pump drive solutions, soft starters, and application support for global industrial projects. We look forward to turning the connections made at CIIF 2026 into reliable, long-term cooperation. 

Read More »
VEIKONG VFD fault codes infographic showing overcurrent, overvoltage, undervoltage, and overload trips.

VFD Fault Codes Explained

VFD Fault Codes Explained: Overcurrent, Overvoltage, Undervoltage, and Overload Trips (Causes and Fixes) Variable frequency drives protect both the motor and the equipment they run. When a drive detects a condition outside safe limits, it stops the process and displays a fault code. For plant engineers and maintenance teams, the priority is to find the cause quickly and correct it before production is affected. A trip does not always mean the drive is faulty. Many events that appear to be drive failures begin elsewhere, in the wiring, the mechanical load, or the incoming supply. Accurate diagnosis depends on reviewing the whole system, not only the drive. This guide explains four common trips: overcurrent, overvoltage, undervoltage, and overload. For each one, it outlines the typical causes and the recommended corrective actions. Quick Comparison of the Four Trips Trip Typical Trigger First fix to try Overcurrent Loose connections, damaged wires, mechanical friction, fast acceleration, heavy starting load   Check wiring, run autotuning, lengthen acceleration time. Overvoltage Quick deceleration, overhauling loads, supply voltage spikes Lengthen deceleration time, stabilize the supply, add braking resistors or a regenerative supply   Undervoltage Supply voltage too low, grid fluctuations Measure input voltage and DC bus, confirm the supply matches the drive rating   Overload Undersized drive, starting torque or surge loads, heat Recheck sizing with margin, clean and cool the drive, consider derating   What Is a VFD Fault Code? A VFD fault code is the drive’s way of naming the problem it detected before it stopped. Frequency converters help keep production stable through fault diagnosis. They point to process problems, and sometimes the drive itself needs repair or replacement. First Steps Before You Reset Anything A few quick checks save a lot of guessing: Overcurrent Trips Overcurrent means the drive saw more current than it should. It is one of the most common trips, and the cause is often simple. Common causes How to fix it Overvoltage Trips Overvoltage shows up most often when a motor slows down fast. During quick deceleration, the motor acts like a generator and sends energy back into the drive. Voltage spikes on the supply side can cause the same trip. Overhauling loads, where machine inertia keeps pushing the motor, do it too. How to fix it Veikong Electric lists a braking chopper, an aluminum resistor, and a ripple resistor, each with its own datasheet. Check the datasheet for ratings, and confirm the match with the technical team before ordering. Undervoltage Trips Undervoltage refers to a supply that is too low. A low supply can also make a drive stop for reasons that look unclear at first. What to check If the drive stops for no clear reason Use this short routine: Overload Trips Overload happens when the drive is asked for more than it can deliver. The most common reason is sizing. A drive that is too small trips out under load. Common causes How to fix it How to Prevent Repeat Trips Is Every Trip a Drive Failure? No, many trips come from loose wiring, a stuck load, supply problems, or heat. Check the system before replacing the drive. How Veikong Backs Its Drives Shenzhen VEIKONG Electric Co., Ltd researches, manufactures, and trades high-, medium-, and low-voltage frequency inverters, and has been doing so since 2004. Its products follow ISO9001 quality management and meet ISO, CE, and IEC standards. Before delivery, each product passes a 12-hour power-on aging test in a high-temperature chamber, then a final full-load test. Support includes: Overcurrent often points to wiring, friction, or fast acceleration. Overvoltage usually comes from quick stops, so slow the deceleration or add braking. Undervoltage means checking the supply and the signals. Overload is mostly about sizing, starting torque, and heat. Read the code, check live values, and ask what changed on the machine. Need help with a drive that keeps tripping, or choosing the right size? Email infoveikong-electric.com, call +86-0755-89587650, or message on WhatsApp at +86 15989436541. For technical support, write to Service@veikong-electric.com.

Read More »
Braking choppers and resistors for safely and quickly stopping electric motors

Braking Choppers and Resistors Explained: How to Stop a Motor Safely and Fast

Ask anyone who runs heavy equipment which part of the cycle worries them most, and many will say the stop. A motor that starts slowly is an inconvenience. A motor that won’t stop when it should is a risk to people, loads, and machines.  That is why braking gets real attention in lifting, pumping, and other industrial work. A stop often needs to be quick. It also needs to be controlled. Getting both takes the right drive and, in many cases, the right braking parts.   This post looks at how a drive fits into the picture, which braking products Veikong Electric offers, and what to prepare before choosing a setup.  Start With the Drive  Braking makes more sense once you know what a variable frequency drive (VFD) does. Veikong Electric describes it as an electronic system that controls an AC induction motor. It manages torque, speed, and direction, and it brings the motor up to speed at a controlled rate.  The company says a VFD system has three parts:  Stopping is built into drive control from the start. Braking parts extend it.  When Does a VFD Make Sense?  Veikong recommends a VFD in several situations. Stopping belongs to the same control picture, so the list is worth knowing. It includes:  The site also notes that VFDs have become compact and versatile over the years, thanks to microprocessors replacing solid-state elements.  The Three Braking Products in Veikong’s Range  Veikong lists these braking-related items in its product menu:  Each one has its own downloadable datasheet. Ratings and model numbers are best confirmed with the technical team, since the datasheets are the place to check exact specifications.  Where Stopping Matters Most: Lifting  Veikong’s clearest braking material is on its hoist and crane page. It describes drives for lifting with reliable braking control, quick stop, and DC excitation control. The stated goal is a system that is safe, reliable, and efficient.  The page also says the company offers several drive types for lifting work: translational structural, full inverter, and dynamic braking frequency inverter. Cranes and hoists differ a great deal, so the right choice depends on the machine.  The idea behind the brake control is simple. Electrical braking is set up to match mechanical braking. Together they act as a protective lock on the system.  What Else a Lifting Drive Needs to Do  Stopping is only part of the picture. A lifting drive also has to hold a load steadily at low speed and work alongside other motors. Veikong’s page lists these features:  These drives are used for lifting, pitching, luffing, wheelbarrow, gyration, and grabbing work.  Other Parts in the Same Product Family  A braking setup rarely stands alone. Veikong groups several support products in the same catalog, so a buyer can look at the whole drive system in one place.  Chokes (reactors):  Filters:  Alongside these sit the drive ranges themselves, including the VFD500, VFD530, VFD550, and VFD580, as well as bypass and online soft starters. Seeing the full range helps when a project needs more than one part.  Choosing a Braking Setup: What to Have Ready  Veikong’s site does not publish a sizing formula for choppers and resistors, so the safest route is to talk to the technical team early. Arrive with clear answers to a few questions.  Clear answers here save time and lead to a better match.  Who Is Behind These Products?  Shenzhen VEIKONG Electric Co., Ltd. researches, manufactures, and trades high-, medium-, and low-voltage frequency inverters. It gives 2004 as its founding year and reports more than 20 years of experience.   The team says it has that same depth of experience in theoretical research, product development, and quality management. Its drives use SPWM, sensorless vector control, and vector and torque control technology.  On quality and standards, the site says:  There are various industries using Veikong products, including petroleum, chemical, melting, hoisting, electric power, building materials, water supply, plastics, textiles, printing, and packing.  Read Also: How to Size a VFD for Your Motor: A Complete kW/HP Selection Guide   Summary  A motor needs a good stop as much as a good start. A VFD gives control over speed, torque, and direction, and braking choppers and resistors support the stopping side of the job. Veikong Electric lists a Braking Chopper, an Aluminum Resistor, and a Ripple Resistor. It also builds lifting drives around reliable brake control, quick stop, and DC excitation.  If you are planning a braking setup, gather your motor, drive, and application details first. Then check the datasheets and confirm the match with the Veikong team before you order. 

Read More »